DESIGN FEATURES
Data Aire's Mini Ceiling Series is the perfect
environmental control system for small computer centers, electronic, telephone,
and battery rooms, or wherever spot cooling may be necessary and space is a
problem. While vertical supply/return air units are designed to fit in a 2 ft x
4 ft standard T-bar ceiling grid space, horizontal units hang in the ceiling
space with duct work connected to supply and return connections. The system
offers an unsurpassed combination of features and options along with a high
standard of performance. Mini Ceiling Systems are available as air cooled, water cooled, or chilled water systems with a
variety of return and supply air arrangements. Air cooled can be specified as
packaged indoor units or split systems with either remote outdoor condensers or
condensing units.
CONTROLS
Precise temperature regulation is provided by a built-in control
system. All electrical components, including
capacitors, contactors, relays and control transformers are pre-wired and
contained in an electrical box that is hinged and swings out for easy access
and servicing. A factory installed microswitch will disable the unit prior to
condensate pan overflow should the drain line become plugged with debris. Each
unit is shipped with a thermostat and subbase as standard. A red indicator
light is unit mounted to indicate a condensate problem. Units with the optional
Data
Alarm Mini Processor II have a condensate pan high water level alarm
standard.
CABINET
Units are designed with a supply and return air plenum that fits
in a 2 ft. x 4 ft. opening of a standard dropped ceiling grid. The field
installed supply and return air plenum is constructed of aluminum and finished
with off-white textured paint. Both the supply and return air grilles are
hinged for easy access when replacing filters. A 2 inch, 60% efficient filter
(based on ASHRAE Std. 52-76) is provided behind the return air grille. Mini
Ceiling Systems are constructed with tubular steel frames for strength
and service access. Removable panels of galvanized steel are lined with 1/2
inch thick, closed cell insulation for quiet and efficient operation.
EVAPORATOR SECTION
The evaporator coil contained in each unit is constructed with
copper tubes and aluminum fins mounted in a stainless steel drain pan. The
drain pan is made witha bottom drain connection and installed in a manner that
provides a positive drain to prevent standing water in the condensate pan. The
refrigeration circuit includes a scroll compressor with internal overload
protection and crankcase heater. The circuit includes an expansion valve with
an external equalizer, filter drier, sight-glass, and high and low pressure
safety switches. The high and low pressure safety switches are connected to the
refrigerant system with a Schrader fitting that allows replacement without
affecting the refrigerant charge, making recovery unnecessary.
The blower assembly is a draw-through type with a centrifugal,
forward curved, double width, double inlet blower
configuration engineered for quiet, reliable operation. The belt driven
variable pitch drive provides adjustable air flow capability to match the
requirements of the controlled space. The draw-through design insures even
distribution across the coil, low internal cabinet losses, and static sealing
of the filter section. The motor has internal overload protection and is
mounted on an adjustable slide base.
SELF-CONTAINED UNITS
Air Cooled - The cabinet houses the evaporator section,
evaporator blower assembly, filter section (located in air distribution plenum)
and the condenser coil. The condenser coil is constructed of copper tubes and
aluminum fins. The condenser blower section is field installed. The condenser
fan is double inlet, double width, with direct drive type
two-speed motor that is controlled with a temperature operated switch. The
condenser blower motor electrical connection is through a factory wired plug.
Water Cooled - The cabinet houses the evaporator section,
evaporator blower assembly, and filter section (located in air distribution
plenum). In addition, a high efficiency coaxial condenser with head pressure
activated 2-way water regulating valve is built into the refrigeration system
and is contained in the evaporator section. The capillary tube connection from
the water regulating valve to the refrigerant system is connected with a
Schrader fitting that allows replacement without affecting the refrigerant
charge, making recovery unnecessary.
Chilled Water - All components are housed within the cabinet.
Chilled water units utilize an existing chilled water loop. Chilled water flow
is controlled by a 2-way valve for accurate and economical temperature control
and dehumidification. The maximum operating water pressure is 150 psi.
SPLIT SYSTEMS
Air cooled systems are available with an outdoor condensing unit
or remote air cooled condenser.
Outdoor Condensing
Unit - The
outdoor condensing unit contains the scroll compressor, sight-glass, filter
drier, high and low pressure safety switches, and condenser coil. The high and
low pressure safety switches are connected to the refrigerant system with a
Schrader fitting that allows replacement without affecting the refrigerant
charge, making recovery unnecessary. The condenser coil is constructed with copper
tubes and aluminum fins. Air discharge is vertical.The condenser fan is
variable speed for head pressure control down to -20 degrees F. The capillary
tube connection from the fan speed control to the refrigerant system is
connected with a Schrader fitting that allows replacement without affecting the
refrigerant charge, making recovery unnecessary. Field piping and wiring is
required from the condensing unit to the indoor evaporator section.
Remote Outdoor Air
Cooled Condenser -
Condensers are industrial duty design with galvanized corrosion resistant
housing, aluminum finned/copper tube coils, coated fan guard, energy efficient,
thermally protected motor, and variable fan speed control with an integral
factory wired and tested control panel. The capillary tube connection from the
fan speed control to the refrigerant system is connected with a Schrader
fitting that allows replacement without affecting the refrigerant charge,
making recovery unnecessary. Air discharge is vertical. Field piping and wiring
is required from the condenser to the indoor compressor/evaporator section.
OPTIONS
Data Alarm Mini
Processor II - The
microprocessor based Data Alarm Mini
Processor II is wall mounted and has a single row, 16 character liquid
crystal display (LCD) in clear vernacular format. The Data Alarm Mini Processor II not only controls and monitors your
room's temperature, humidity, air flow and cleanliness, but also provides alarm
history and an automatic self-test of the microprocessor system start-up.
Multiple messages will be displayed by automatically scrolling from each
message to the next. Multiple alarms will be displayed sequentially in order of
occurrence.
Operation - Unit on/off operation is controlled by a
slide switch and push button control switches which allow menu selection for
programming, operational information, diagnostics, and historical data. A
password feature prevents unauthorized access. Menu programmed information for
basic system operation and alarm parameters is
non-volatile.
Programmable
Functions/Monitoring -
The user friendly switch permits step-by-step programming and display of the
following functions:
• Temperature Setpoint - (60-80 deg F, 15.6-26.7 deg C)
• Temperature Sensitivity - (+1 to + 5 deg F or .5 to 2.7 deg C)
• Humidity Setpoint - (30-70% RH)
• Humidity Sensitivity - (+1 to +15% RH in 0.1% increments)
• Temperature Alarm Points - (50-90 deg F, 10-32.2 deg C)
• Humidity Alarm Points - (10-90% RH)
• Unit Start Time Delay
• Interstage Time Delay
• Password 1st Level
• Password 2nd Level
• Audio Alarm Level
• Restart Mode
• Firestat Trip Temperature
• Local Alarm Function
Normal functions are monitored and displayed on the LCD and
include, in addition to the above set points, the following:
• Current Temperature (° F or ° C)
• Current Humidity (% RH)
• Cooling
• Reheat
• Humidification
• Dehumidification
• Date and Time
Alarms - Alarm conditions are monitored on the LCD and
are enunciated by an audible alarm. The alarm silence button will quiet the
audible alarm but the display will continue to indicate the alarm condition
until the problem is corrected. The following alarms are standard:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• Compressor High Pressure
• Compressor Short Cycle
• High Condensate Water
• Firestat Tripped
• No Air Flow Alarm
• Temperature Sensor Failure
• Humidity Sensor Failure
Historical Data -The current temperature and humidity, with
minimum and maximum readings for the last 24 hours of operation can be recalled
and displayed. Alarm history of the last five alarms is maintained in
sequential order.
Diagnostics - Automatic and manual diagnostics sequences
simplify troubleshooting.
Each Data Alarm Mini
Processor II is shipped with 25 feet of cable for field connection, (additional
cable is available). Contact factory for cable lengths in excess of 75 feet.
Remote Mounted
Temperature & Humidity Sensors
Temperature and humidity sensors are provided in a wall mounted
plastic case for remote sensing of temperature and humidity. Standard unit
sensors are removed. Requires field wiring of (field provided) shielded cable. Remote temperature and humidity sensors option only available when
used with the Data Alarm Mini Processor
II.
Steam Generator
Humidifier
The steam generator humidifier eliminates air contamination caused
by mineral deposits. The totally self-contained system includes a quick change,
disposable cartridge and automatic flush cycle. Steam
generator humidifier option only available when used with the Data Alarm Mini
Processor.
Electric Reheat
Low-watt density finned tubular sheathed coils are constructed of
stainless steel and provide ample capacity to maintain room drybulb conditions
on a call for dehumidification. Low-watt density coils eliminate ionization
associated with open wire electrical resistance heating. Over-heat switches are
provided. Electric reheat is available in 2, 4, or 5 KW capacities, shipped
factory installed with high limit cut-out.
Low Ambient Control
Damper
A low ambient control damper is available for use with ducted
outside condenser air. The low ambient control damper kit is field installed
and consists of a 14" x 14" damper section and head pressure
operator. The low ambient control damper allows unit to operate down to -30 degrees
F (-34.4 degrees C). The capillary tube connection from the head pressure
control to the refrigerant system is connected with a Schrader fitting that
allows replacement without affecting the refrigerant charge, making recovery
unnecessary.
Condensate Pumps
Condensate pumps can be provided for field mounting or factory
installed and wired. The pump body can be placed within the unit coil pan.
Maximum 8 ft. head. Field installed condensate pumps require either separate
110 or 230 volt power source.
Horizontal, Front,
Side Supply Air
Units may be ordered with optional horizontal supply air
configurations of front or either side. Optional supply air converts unit for
ducted supply air connection.
Side Return Air
Units may be ordered with optional side return consisting of a
factory modified flanged for ducting return air. Optional side return air
converts unit for ducted return air connection. An additional option provides
ceiling mounted return air filter grille, ceiling mounted return air filter box
with hinged grille and filter for duct connection. Filter included with this
option is a 20" x 20" x 4" deep, 30% efficient (based on ASHRAE
Std. 52-76) pleated filter.
Extended Compressor
Warranties
Extended compressor warranties are available for periods of twenty-four (24) or forty-two (42) months in addition to the standard factory eighteen (18) month warranty. These warranties are for the replacement of compressors and do not include labor.