CONTROL SYSTEM
Standard units are shipped with a thermostat and sub-base for remote
wall mounting. An optional wall mounted microprocessor is available (See Mini
Data Alarm Processor-II Options Section).
ELECTRICAL
All electrical components including capacitors, relays, and
control transformers are pre-wired. Each unit is provided with a microswitch to
prevent condensate pan overflow. The microswitch will disable the unit prior to
pan overflow should the drain line become plugged with debris.
ELECTRIC REHEAT
6 kW reheat is standard on 2.5 through 4 ton Mini-Plus units (5
ton Mini-Plus units have 6 kW reheat on single phase and 12 kW reheat on three
phase). Electric reheat is accomplished with low watt, low density finned tube
fabricated of stainless steel core sheath with plated fins to withstand moist
conditions. Reheat is installed on the air discharge side of the cooling coil
and provides ample capacity to maintain room drybulb conditions during
dehumidification. Low-watt density coils eliminate ionization associated with
open air electric resistance heating.
CABINET
Mini-Plus indoor sections are constructed with tubular steel
frames for strength and service access. Removable galvanized steel panels are
lined with 1 inch thick, 1-1/2 pound density insulation for quiet and efficient
operation. An integral filter section with 2" filters is standard.
AIR COOLED - PACKAGED SYSTEM
Evaporator Section - The evaporator section is a draw-through type
with double width, double inlet blower with belt drive and variable pitch
sheave. The self-aligning ball bearings are rated for a minimum life of 100,000
hours. The evaporator coil is constructed of copper tubes and aluminum fins.
The single stage refrigeration circuit includes an expansion valve with
external equalization. A stainless steel drain pan is standard. Field supplied
return and supply air ductwork is required for all Mini-Plus evaporator
section.
Condensing Unit
Section - The
attached condensing unit contains a scroll compressor with crankcase heater,
filter drier, sight glass, and condenser coil. The condenser coil is constructed
with copper tubes and aluminum fins. The condenser blower is double inlet,
double width with belt drive and variable pitch sheave.
AIR COOLED - SPLIT SYSTEM with INDOOR
CONDENSING UNIT
Evaporator Section - The evaporator section is a draw-through type
with double width, double inlet blower with belt drive and variable pitch
sheave. The self-aligning ball bearings are rated for a minimum life of 100,000
hours. The evaporator coil is constructed of copper tubes and aluminum fins.
The expansion valve with external equalization is contained in the evaporator
section.. A stainless steel drain pan is standard.
Field supplied return and supply air ductwork is required for all Mini-Plus
evaporator sections.
Condensing Unit - The condensing unit contains a scroll
compressor with crankcase heater, filter drier, sight glass, and condenser
coil. The condenser coil is constructed with copper tubes and aluminum fins.
The condenser blower is double inlet, double width with belt drive and variable
pitch sheave. Field piping and wiring is required between the indoor evaporator
and condensing unit sections.
AIR COOLED - SPLIT SYSTEM with INDOOR
CONDENSER
Evaporator/Compressor
Section - The evaporator
section is a draw through type with double width, double inlet blower with belt
drive and variable pitch sheave. The self-aligning ball bearings are rated for
a minimum life of 100,000 hours. The evaporator coil is constructed of copper
tubes and aluminum fins. The expansion valve with external equalization is
contained in the evaporator section. A stainless steel drain pan is standard.
The condensing section is contained in a "side car" and attached to
the evaporator section.
The condensing section - includes a scroll compressor with crankcase
heater, filter drier and sight glass. Field supplied return and supply air
ductwork is required for all Mini-Plus evaporator sections. Condenser Section
The condenser section includes a condenser coil and condenser blower. The
condenser coil is constructed of copper tubes and aluminum fins. The blower is
double inlet, double width with belt drive and variable pitch sheave. Field
piping and wiring is required between the indoor evaporator/compressor and the
condenser sections.
AIR COOLED - SPLIT SYSTEM with OUTDOOR
CONDENSING UNIT
Evaporator Section - The evaporator section is a draw-through type
with double width, double inlet blower with belt drive and variable pitch
sheave. The self-aligning ball bearings are rated for a minimum life of 100,000
hours. The evaporator coil is constructed of copper tubes and aluminum fins.
The single stage refrigeration circuit includes an expansion valve with
external equalization. A stainless steel drain pan is standard. Field supplied
return and supply air ductwork is required for all Mini-Plus evaporator
section.
Outdoor Condensing
Unit - The
condensing unit contains a scroll compressor with crankcase heater, filter
drier, sight glass, and condenser coil. The condenser coil is constructed with
copper tubes and aluminum fins. The galvanized steel housing and fan guard
powder coated for longer life. The energy efficient condenser fan is thermally
protected. Air discharge is vertical. The condenser fan is variable speed for
head pressure control to -20° F ambient conditions. Field piping and wiring is
required between the indoor evaporator section and the outdoor condensing unit.
AIR COOLED - SPLIT SYSTEM with OUTDOOR
CONDENSER
Evaporator/Compressor
Section The
evaporator section is a draw through type with double width, double inlet
blower with belt drive and variable pitch sheave. The self-aligning ball
bearings are rated for a minimum life of 100,000 hours. The evaporator coil is
constructed of copper tubes and aluminum fins. The expansion valve with
external equalization is contained in the evaporator section. A stainless steel
drain pan is standard.
The compressor
section is
contained in a "side car" and attached to the evaporator section and
includes a scroll compressor with crankcase heater, filter drier and sight
glass. Field supplied return and supply air ductwork is required for all
Mini-Plus evaporator sections.
Outdoor Condenser
Section The
outdoor condenser includes a condenser coil, integral factory wired panel and
condenser fan motor. The condenser coil is constructed of copper tubes and
aluminum fins. The thermally protected fan motor is variable speed for head
pressure control to -20° F ambient conditions. The galvanized steel housing is
powder coated for longer life. Field piping and wiring is required between the
indoor evaporator/compressor and the condenser sections.
WATER COOLED - PACKAGED SYSTEM
Evaporator Section - The evaporator section is a draw-through type
with double width, double inlet blower with belt drive and variable pitch
sheave. The self-aligning ball bearings are rated for a minimum life of 100,000
hours. The evaporator coil is constructed of copper tubes and aluminum fins.
The single stage refrigeration circuit includes an expansion valve with
external equalization. A stainless steel drain pan is standard. Field supplied
return and supply air ductwork is required for all Mini-Plus evaporator
section.
Compressor Section - The attached compressor section includes a
scroll compressor with crankcase heater, filter drier, sight glass, coaxial
condenser and head pressure water regulating valve. Maximum water pressure is
150 psi. A dry cooler (fluid cooler) or water cooling source is required on
water cooled systems.
WATER COOLED - SPLIT SYSTEMS
For applications with space restrictions water cooled systems may
be ordered as split systems. The evaporator section and compressor sections
(see Water Cooled - Packaged Systems) are shipped separately. Field piping and
wiring is required between the evaporator and compressor sections. Field
supplied return and supply air ductwork is required for all Mini-Plus
evaporator sections. A dry cooler (fluid cooler) or water cooling source is
required on water cooled systems.
CHILLED WATER SYSTEMS
Blower Section/Coil
Section - The
blower section contains a double width, double inlet blower with belt drive and
a variable pitch sheave and blower motor. The self-aligning ball bearings are
rated for a minimum life of 100,000 hours. The chilled water coil and chilled
water valve are housed in the blower section as well. The chilled water coil is
constructed of copper tube and aluminum fins. Utilizing chilled water from an
existing chilled water loop, water flow is controlled by a 2-way valve for
accurate and economical temperature control and dehumidification. The drain pan
is constructed from stainless steel. Field supplied return and supply air
ductwork is required for all Mini-Plus blower sections.
EXTENDED COMPRESSOR WARRANTIES
Extended compressor warranties are available for periods of twenty-four (24) or forty-two (42) months in addition to the standard factory eighteen (18) month warranty. These warranties are for the replacement of compressors and do not include labor.