DESIGN FEATURES
CABINET
The heliarc welded tubular steel frame provides maximum strength
and ease of service access. Removable panels of galvanized steel are insulated
with 1 inch thick, 1-1/2 pound density insulation for thermal protection and sound
attenuation. All parts are easily accessible. The electrical panel is hinged
and swings out for servicing.
COIL SECTION
Designed for draw through application, the computer selected coil
offers greater efficiency in the cooling and dehumidification process. Air
bypass is provided to prevent saturated air from being introduced into the
controlled space. The coil section is provided with a stainless steel drain
pan.
FAN SECTION
The centrifugal, forward curved, double width, double inlet blower
configuration is engineered for quiet reliable operation. The belt driven
variable pitch drive section provides adjustable air flow capability to match
load requirements of the controlled space. The draw through design insures even
air distribution across the coil and bypass, low internal cabinet losses, and
static sealing of the filter section. Motors are mounted on an adjustable slide
base and have internal overload protection.
FILTER SECTION
Units are provided with 4 inch deep pleated design, 30% efficient
filters (based on ASHRAE Std. 52-76). The filter section is an integral part of
the system and is accessible from either side.
REHEAT
Two stage electric reheat is standard. Low-watt density finned
tubular sheathed coils are constructed of stainless steel and sized to maintain
room dry bulb conditions during a call for dehumidification. Low-watt density
coils eliminate ionization associated with open air electric resistance
heating.
REFRIGERATION CIRCUIT
LCS™ is available with either a single or dual refrigeration
circuit. The refrigeration circuit includes a hermetic scroll compressor. These durable, heavy duty, fully welded compressors have no
gaskets or seals, eliminating the possibility of refrigerant or oil leaking
into the controlled space or environment. Scroll compressors also bring a
combination of reliability, efficiency, and improved system sound performance.
The refrigeration circuit includes built-in compressor overload protection,
crankcase heater, filter drier, sight-glass, adjustable expansion valve with
external equalizer, low pressure override timer (air cooled units), manual
reset high pressure control, and compressor short cycle timer.
Water/glycol cooled units include a plate fin condenser sized to
provide the required capacity for heat rejection with minimum water/glycol flow
and low total pressure drop. Head pressure regulating valves control the
condensing temperature and maintain required capacity at various water/glycol
flow rates and temperatures.
Air Cooled with
Remote Outdoor Condenser
A wide range of outdoor condensers are available. Condensers are
manufactured by Data Aire and sized to meet heat rejection and ambient
conditions as required. The industrial duty design includes galvanized
corrosion resistant housing, aluminum finned copper
tube coils, coated fan guards, energy efficient thermally protected direct
drive motors, and variable fan speed control on lead motor for proper control
down to -20° F ambient temperatures. Additional fan motors are controlled with
ambient thermostats.
Air Cooled with
Outdoor Condensing Unit
When compressors are required to be out of the controlled space,
LCS™ is available with a remote outdoor condensing unit. The condensing unit
includes hermetic scroll compressor(s) with built-in overload protection,
crankcase heater, filter drier, sight-glass, and condenser coil. The coil is
constructed with copper tubes and aluminum fins. The housing is galvanized
steel with vertical air discharge. The condenser fan motor is variable speed
type for head pressure control down to -20° F ambient temperatures. Additional
fan motors are controlled by ambient fan thermostats.
Water/Glycol Cooled
with Remote Outdoor Dry Cooler
Remote outdoor dry coolers are available in a variety of sizes.
Each dry cooler includes galvanized corrosion resistant housing, aluminum
finned copper tube coil, coated fan guards, surge
tank, pump contactor, and energy efficient thermally protected direct drive
motors. Dry coolers with multiple motors have cycling control.
CHILLED WATER SYSTEMS
Chilled water systems include all the same features of the LCS™
product line. Designed for draw through application, the computer selected coil
offers greater efficiency in the cooling and dehumidification process. Air
bypass is provided to prevent saturated air from being introduced into the
controlled space. Chilled water flow is controlled by a 3-way chilled water
valve for accurate and economical temperature control and dehumidification.
CONTROL SYSTEM
Unit control is maintained with the microprocessor based Mini
Data Alarm Processor-II. The Mini Data Alarm Processor-IIis a
wall mounted, one row, 16 character control that not only monitors the
controlled environment's humidity, air flow, and cleanliness, but also provides
alarm history and an automatic self-test of the microprocessor on system
start-up. Multiple messages are displayed by automatically scrolling from each
message to the next. All messages are presented in a clear vernacular format on
the liquid crystal display (LCD). Multiple alarms are displayed sequentially in
order of occurrence.
OPERATION - A slide switch allows unit on/off operation:
push buttons allow menu selection for programming, operational information,
diagnostics, and historical data. The two-level password feature prevents
unauthorized access. Menu programmed information for basic system operation and
alarm parameters is non-volatile.
PROGRAMMABLE FUNCTIONS -
The user friendly MENU and SELECT push buttons permit step-by-step programming
of the following selections:
Temperature Setpoint: 65-85° F/18.3-29.4° C
Humidity Setpoint: 30-70% RH
Temperature Deadband: ±1-5° F/C in 0.1° Increments
Humidity Deadband: ±1-15% RH in 0.1% increments
Temperature Alarm Points
Humidity Alarm Points
Calibrate Temperature Sensor
Calibrate Humidity Sensor
Unit Start Time Delay
Interstage Time Delay
Password - 1st Level
Password 2nd Level
Audio Alarm Level
Restart Mode
Firestat Trip Temperature
Local Alarm
DISPLAYED CONDITIONS, DATA, & FUNCTIONS - The Mini Data Alarm
Processor-II displays and monitors the following conditions, data, and
functions:
Temperature Setpoints
Humidity Setpoint
Current Temperature
Current Humidity
Cooling 1, 2 (as applicable)
Reheat
Humidification
Dehumidification
ALARMS - Alarm conditions are displayed and monitored on
the microprocessor LCD along with an audible alarm. The alarm silence switch
will quiet the audible alarm but the display will continue to indicate the
alarm condition until it is corrected. The following alarms are displayed:
High Temperature Warning
High Humidity Warning
Low Temperature Warning
Low Humidity Warning
Compressor High Pressure
High Condensate Water
Firestat Tripped
No Air Flow
Compressor Short Cycle
Low Voltage Warning
Temperature Sensor Failure
Humidity Sensor Failure
HISTORICAL DATA -
Temperature and humidity, with the minimum and maximum readings since the last
power on can be recalled and displayed. Alarm history is maintained in
sequential order (up to 5 alarms).
DIAGNOSTICS - Automatic and manual diagnostics sequences
simplify troubleshooting.
In addition, the Mini Data
Alarm Processor-II has an inclusive seven-day programming format for
unoccupied (low demand) periods. This secondary schedule can minimize equipment
run times, reducing energy consumption and provide user cost savings.
The following
selections can be adjusted to match the requirements needed for unoccupied (low
demand) periods.
• Cooling Setpoint for Secondary Schedule
Adjustment Range: 1 - 30° F above the "occupied" Temperature Setpoint
• Reheat Setpoint for Secondary Schedule
Adjustment Range: 1 - 30° F below the "occupied" Temperature Setpoint
• Dehumidification Setpoint for Secondary Schedule
Adjustment Range: 1 - 30% RH above the "occupied" Humidity Setpoint
• Humidification Setpoint for Secondary Schedule
Adjustment Range: 1 - 30% RH below the "occupied" Humidity Setpoint
• Day Schedule
Scheduling for each day of the week or any
combination of days
"Unoccupied" Adjusted Setpoint
Operation
Adjusts to Temperature and Humidity Setpoints to
Secondary Schedule
"Unoccupied" ON/OFF Operation
During "unoccupied" schedule:
cooling - off
heating - off
humidification - off
dehumidification - off
fan - off
• Override Request
Override Secondary Schedule
Adjustment Range: 1 - 12 hours
OPTIONS
Energy Saver Coil - An Energy Saver Coil
can be provided integral to the unit matching the nominal capacity. Energy Saver cooling is available
whenever the incoming water/glycol temperature is below the setpoint of the
water sensing changeover thermostat. The water sensing changeover thermostat is
factory set at 45° F/7.2° C. The water sensing changeover thermostat is field
adjustable. The Energy Saver>
operates during a need for cooling. The Energy
Saver valve will open at setpoint plus deadband. When the space temperature
falls to setpoint, the valve will close and the space is considered satisfied.
While in Energy Saver mode with the
valve open, if the incoming water/glycol temperature rises 3° F above the
setpoint (of the water sensing thermostat), the Energy Saver valve will close and DX (mechanical) cooling will
begin. Option includes a 3-way pressure control valve on the condenser water
circuit(s) and a 3-way valve for the economy coil. Common piping for the coil
and condensers is provided.
Auxiliary Chilled Water Coil - Where an existing chilled water loop is
available, units can be fitted with an auxiliary chilled water coil. Units will
operate using the chilled water for cooling. Upon a loss of water flow or an
increase in room temperature the system will bring on compressor (DX) cooling.
The Auxiliary Chilled Water Coil option includes the next size motor. Separate
piping is provided for the chilled water coil and refrigeration connections on
air cooled units or water circuit(s) on water/glycol cooled units.
Unit Mounted Temperature & Humidity Sensors - Temperature and humidity sensors may be ordered
for unit mounting in the return air.
Unit Mounted Disconnect - A unit mounted non-automatic disconnect switch is installed in
the high voltage electrical section. The operating mechanism prevents access to
the high voltage electrical components until switched to the "OFF"
position. The operating mechanism (handle) protrudes through the exterior unit
panel.
Hot Water Reheat - Where hot water is available, a water coil for reheat is offered.
The coil is designed for 150 psi maximum water pressure and includes a 2-way
valve (a 3-way is also available). Units with the hot water reheat do not
include electric reheat.
Hot Gas Reheat - The unit's hot gas discharge may be used for reheat for maximum
system efficiency.
Steam Generator Humidifier - Units may be furnished with an electric steam generator
humidifier with "quick change" disposable cylinders and auto-flush
cycle. The steam generator humidifier with its patented control system
optimizes cylinder life by concentrating incoming water to a predetermined
conductivity much higher than that of any entering water. The control system
continuously monitors the conductivity in the cylinder through its electronics
which allows water to be flushed as often as is necessary to maintain the level
at this design conductivity. The high design conductivity results in a minimum
flushing of heated water which saves energy. The humidifier is designed to
allow all units at any voltage to produce full rated steam output at an optimum
low water level. Available in 10 and 30 pound per hour
capacities.
Hot Gas Bypass - Hot gas bypass may be ordered for changing load conditions. The
hot gas bypass valve is installed between the compressor discharge line and the
leaving side of the expansion valve through a side outlet distributor. The system
with the evaporator under full load will maintain pressure on the leaving side
of the hot gas bypass valve to keep the valve port closed. Should the load on
the evaporator decrease to the point where the coil is below the desired
setting, the pressure on the discharge of the hot gas bypass will put pressure
on the diaphragm overcoming the spring pressure of the seat and allowing some
hot gas to mix with the normal liquid discharge of the expansion valve raising
the evaporator pressure. This reduces the cooling capacity of the unit to match
the load. The hot gas bypass valve can be adjusted to "fine tune" the
unit to room conditions.
3-Way Water Regulating Valve - A 3-way water regulating valve for pressure
control may be ordered to replace standard 2-way valve installed in the unit.
The 3-way valve controls the water/glycol flow rate to maintain the required
capacity under varying conditions.
Condensate Pump - Condensate pumps may be ordered as factory installed or for field
installation. Condensate pumps are complete with sump, motor, and automatic
control. The pumps are rated for 130 GPM @ 20 foot maximum or 40 GPH @ 20 feet
with check valve. Pumps shipped loose are available in 115, 230, or 460 volt.
Extended Compressor Warranties - Extended compressor warranties are available for periods of twenty-four (24) or forty-two (42) months in addition to the standard factory eighteen (18) month warranty. These warranties are for the replacement of compressors and do not include labor.