DESIGN FEATURES
FRAME/CABINET
The heliarc welded
tubular steel frame provides for maximum strength and ease of access with
minimum space requirement. Side and front panels can be easily opened and
removed with quarter-turn fasteners, allowing full access to all unit
components. All panels include 1 inch thick, 1-1/2 pound density insulation for
protection and sound attenuation. All parts are easily accessible.
COIL SECTION
Designed for draw
through application, the computer selected coil offers greater efficiency in
the cooling and dehumidification process. Air bypass is provided to prevent
saturated air from being introduced into the controlled space. The coil section
is provided with a stainless steel drain pan.
FAN SECTION
The centrifugal,
forward curved, double width, double inlet blower configuration is engineered
for quiet reliable operation. The belt driven variable pitch drive provides
adjustable air flow capability to match load requirements of the controlled space.
The draw through design insures even air distribution across the coil, low internal
cabinet losses, and static sealing of the filter section. Motors are mounted on
an adjustable slide base and have internal overload protection.
FILTER SECTION
Units are provided
with 4 inch deep, 30percent efficient filters (based on ASHRAE Std. 52-76). The
filter section is accessible from the top or side on downflow units and the right
hand side on upflow units.
REHEAT
Three stage electric
reheat is standard. Low-watt density finned tubular sheathed coils are
constructed of stainless steel and provide ample capacity to maintain room
drybulb conditions during dehumidification. Low-watt density coils eliminate
ionization associated with open air electric resistance heating.
HUMIDIFICATION
Modular Data Temp
units include an electric steam generator humidifier with a "quick
change" disposable cylinder and an auto-flush cycle. The steam generator
humidifier with its patented control system optimizes cylinder life and energy
efficiency by concentrating incoming water to a predetermined conductivity much
higher than that of the entering water. The control system continuously
monitors the conductivity in the cylinder through its electronics which allows
water to be flushed as often as is necessary to maintain the capacity at this
design conductivity. The high design conductivity results in
a minimum flushing of heated water, thereby saving energy. The humidifier
is designed to allow units at any voltage to produce full rated steam output
capacity at an optimum water level based on the design conductivity.
REFRIGERATION CIRCUIT
The single circuit,
dual stage refrigeration circuit is designed around a high efficiency hermetic
scroll compressor. These durable, heavy duty, fully
welded compressors have no gaskets or seals, substanially reducing the
possibility of refrigerant or oil leaking into the controlled space or
environment. Scroll compressors bring a combination of reliability, efficiency,
and improved system sound performance to the Modular Data Temp line. 2-stage control
is standard. A hot gas bypass valve allows hot gas to be redirected into the evaporator
coil to reduce unit capacity . As the load increases,
the solenoid valve closes at 60 psi (adjustable). Should the evaporator
decrease to the point where the valve is below the desired setting, the
solenoid valve will open allowing some hot gas to mix with the normal liquid
discharge of the expansion valve raising the evaporator pressure. This reduces the
cooling capacity of the unit to match the load. The refrigeration circuit includes
built-in compressor overload protection, crankcase heater, filter drier, sight-glass,
adjustable expansion valve with external equalizer, low pressure override timer
(air cooled units), manual reset high pressure control, compressor short cycle
timer, and rotalock service valves.
Water/glycol cooled
units include a counterflow coaxial condenser sized to provide the required
heat of rejection with minimum water/glycol flow for a low total pressure drop.
Head pressure water regulating valves control the condenser water flow to maintain
proper head pressure under varying load conditions,.
Air Cooled with Remote Outdoor Condenser - A wide range of outdoor condensers is available. Condensers
are manufactured by Data Aire and sized to meet the heat rejection and ambient
conditions as required. The industrial duty design includes galvanized
corrosion resistant housing, aluminum finned copper tube coils, powder coated fan guards, energy efficient thermally
protected direct drive motors, and variable fan speed control on lead fan motor
for proper control down to -20° F. Additional fan motors are controlled with
ambient thermostats.
Air Cooled with Indoor Condenser - A wide range of floor mounted indoor condensers with
horizontal intake and discharge are available for applications where an outdoor
condenser cannot be used. Finished to match the indoor evaporator section, the
condenser includes a centrifugal, forward curved, double width, double inlet blower engineered for quiet, reliable operation.
The belt driven variable pitch drive provides adjustable air flow. The motor
has internal overload protection
and is mounted on an adjustable slide base. Indoor condensers
are provided with a factory mounted and piped receiver, complete with a head
pressure control valve to maintain head pressure under varying ambient
conditions down to -30° F.
Air Cooled with Outdoor Condensing Unit - When compressors are required to be out of the controlled
space, Modular Data Temp units are available with a remote outdoor condensing
unit. The condensing unit includes a hermetic scroll compressor with built-in
overload protection, crankcase heater, filter drier, sight-glass, and condenser
coil. The coil is constructed with copper tubes and aluminum fins. The housing
is galvanized steel with vertical air discharge. The condenser fan is a
variable speed type for head pressure control down to -20° F ambient
temperature. Additional fan motors are controlled by ambient fan thermostats.
Water/Glycol Cooled with Remote Outdoor Fluid
Cooler - Remote outdoor fluid
coolers are available in a variety of sizes. Each dry cooler includes galvanized
corrosion resistant housing, aluminum finned copper tube coil, coated fan guards,
surge tank, motor contactor, pump contactor, and energy efficient thermally protected
direct drive motors. Multiple fan motors are staged to maintain the desired condenser
supply fluid temperature.
CONTROL SYSTEM
The microprocessor
based Data Alarm Processor-II (DAP-II) offers the definitive answer for
precision environmental control. The DAP-II control system not only monitors
temperature, humidity, airflow, and cleanliness, it provide
component runtimes, alarm history, and an automatic self-test of the microprocessor
on system start-up. All messages are presented in a clear vernacular format and
are sequentially displayed on a 2 row, 80 character,
backlit liquid crystal display (LCD).
OPERATION - High reliability, flat, sealed switches with tactile
feedback allow uniton/off operation, menu selection for programming,
operational information, diagnostics, and historical data. Multilevel passwords
prevent unauthorized access. Alarm conditions are enunciated by an audible
alarm. The alarm silence switch will quiet the audible alarm but the display
will continue to indicate the alarm condition until the problem is corrected.
STANDARD FEATURES
• Forward/Backward
Menu Access
• Stand Alone Panel
• All Settings from
Face of Panel
• Factory Calibrated
Temperature Sensor
• Multilevel Password
Access
• Automatic Self-Test
Diagnostics
• Database of Unit
& Room Conditions
• Factory Calibrated
Humidity Sensor
• Database of Unit
& Room Conditions
• All Programmed
Functions Saved in EEPROM
OPERATIONAL FEATURES
• Selectable Control
Type
• Sequential Load
Activation
• Temperature
Anticipation
• Humidity
Anticipation
• Dehumidification
Mode Lockout
• Automatic Reheat
Element Rotation
• Start Time Delay
• Compressor Short
Cycle Control
• Automatic or Manual
Restart
DIAGNOSTICS & SERVICE
FEATURES
• Manual
Diagnostic Program
• Alarms Displayed in
Order of Occurrence
• Adjustable Alarm
Limits
• Four Programmable
Optional Alarms
• Programmable Delays
for Optional Alarms
• Programmable Remote
Alarm
• Select Alarms
Optionally Disabled
• Audio Alarm Tone
• Manual Override
for: Blower, Cool, Heat 1, Humidification, Water Valve
PROTECTIVE & SAFETY
FEATURES
• Metal Shell
Enclosure
• Sealed Front
Control Panel
• Isolation
Transformer
• Opto-Coupler Signal
Inputs
• Protected 24 VAC
Power Input
• Heavy Ground Planes
& Power Foils
• Watch Dog Timer
• Fused RS-485
Network Lines
• Network Bypass
Relays
• Switching Power
Supply
PROGRAMMABLE FUNCTIONS - The user friendly Menu Selection Switches permit
step-by-step programming of the following selections:
• Temperature
Setpoint - 65-85° F/18.3-29.4° C
• Temperature
Deadband - +/- 1-5° F/C in 0.1° increments
• High Temperature
Alarm Limit - 70-90° F/21.1-32.2°C
• Low Temperature
Alarm Limit - 55-75° F/12.8-23.9° C
• Humidity Setpoint -
30-70 percent RH
• Humidity Deadband -
1-15 percent RH
• High Humidity Alarm
Limit - 35-90 percent RH
• Low Humidity Alarm
Limit - 10-65 percent RH
• Mode & Stage
Response Time - 1 to 5 minutes
• Reset Equipment
Times for: Blower, Compressor, Reheat 1, Humidifier,
Dehumidification,
Reset All to Zero
• Audio Alarm Mode:
None, Long, Full
• Automatic Self-Test
Acknowledgment: On, Off
• Manual Diagnostics:
Stay in Normal Menu Mode, Change to Diagnostic Mode
• Humidity
Anticipation: On, Off
• Compressor Short
Cycle Alarm: On, Off
• Dehumidification
Mode: Compressor within Reheat Limits, Compressor with
No
Reheat Limits, Dehumidification Off
• Define Password:
00-99
• Firestat
Temperature Alarm Limit: Unit Shutdown & Alarm @ 100-150° F
• Low Discharge
Temperature Alarm Limit*- 45-60° F/7.2-15.6° C,
Disable
Low Discharge Temperature Alarm
• Power Failure or
Restart Mode: Automatic, Manual
• System Start Delay:
0-10 Minutes in 5 Second Increments
• Message for
Optional Alarm 1, 2, 3, & 4
Custom
Message*
Fan
Motor Overload*
Local
Alarm
Standby
Pump On*
UPS/Alternate
Power On*
Reheat
Inhibited
Humidification
Inhibited
Reheat
& Humidification Inhibited
• Delay for Optional
Alarm 1, 2, 3, & 4: 0-900 Seconds, Off
• Person to Contact
on Alarm
Contact
Message Not Used
Data
Processing Manager
Maintenance
Engineer
Service
Company
25
Space Custom Message*
• Scheduled Normal
Maintenance: 1 - 1000 Hours
• Control Logic:
Smart Logic, PID, Setpoint Deviation
• Reheat Stage: None,
1, 3.Temperature Scale: Fahrenheit, Centigrade
• Calibrate
Temperature Sensor: +9.9° F/C
• Calibrate Humidity
Sensor: + 30percent RH
• Unit & Network
ID Number: 0-260
• Calibrate Discharge
Air Sensor*:+9.9° F/C
• Remote Alarm 1, 2,
3 Selection*
Compressor
Short Cycle
Custom
Message 1, 2, 3, & 4*
Dirty
Filter
Discharge
Air Sensor Problem*
Fan
Motor Overload*
Firestat
High
Humidity
Compressor
High Pressure
High
Temperature
Humidifier
Problem
Humidifier
Sensor Problem
Local
Alarm 1, 2, 3, & 4*
Low
Humidity
Compressor
Low Pressure
Low
Temperature
Low
Voltage
Maintenance
Required
Manual
Override
No
Airflow
No
Water Flow*
Power
Problem or Restart
Smoke
Detector*
Standby
Pump On*
Temperature
Sensor Problem
Water
Detection Probe
UPS/Alternate
Power On
Reheat
Inhibited
Humidification
Inhibited
Reheat
& Humidification Inhibited
• Humidifier:
None
Computer,
Non-Modulating
Computer,
Modulating*
Comfort,
Non-Modulating
Comfort,
Modulating
• Water Valve Voltage Range: 0 - 10 VDC, 4 - 7 VDC, 6 - 9 VDC, 7 - 10 VDC
• Reversing Acting
Valve: Yes, No
DISPLAYED CONDITIONS, DATA & FUNCTIONS - The Data Alarm Processor-II displays and monitors the
following conditions, data, and functions:
• Temperature
Setpoint
• Humidity Setpoint
• Current Temperature
• Current Humidity
• Current Percent of
Capacity Utilized
• Current Discharge
Air Temperature*
• Unit or Network ID
Number
• Zone Number
• Cooling
• Reheat
• Humidifcation
• Dehumidification
ALARMS - Alarm conditions are displayed and monitored on the
microprocessor LCD along with an audible alarm. The alarm silence switch will
quiet the audible alarm but the display will continue to indicate the alarm
condition until it is corrected. The following alarms are displayed:
• High Temperature
Warning
• Low Temperature
Warning
• High Humidity
Warning
• Low Humidity
Warning
• Compressor High
Pressure
• Compressor Low
Pressure
• Under Floor Water
Detection
• No Air Flow
• Dirty Filter
• Humidifier Failure
• Manual Override
• Firestat Tripped
• Low Voltage Warning
• Power Failure
Restart
• Compressor Short Cycle
• Temperature Sensor
Error
• Humidity Sensor
Error
• Maintenance
Required
• Custom Message*
• Local Alarm*
• Discharge Air
Sensor Error*
• Fan Motor Overload*
• No Water Flow*
• Smoke Detector
• Standby Pump On*
• Person to Contact
on Alarm*
*Some of the
programmable selections, displays, or alarms may require additional components
or sensors. Contact your Data Aire representative for a detailed analysis of
your requirements.
HISTORICAL DATA - In order to facilitate maintenance and service, historical
data can be recalled and displayed. The historical database is maintained by
battery back-up should power fail. The following data can be recalled and
displayed:
• High Temperature, Last
24 Hours
• Low Temperature,
Last 24 Hours
• High Humidity, Last
24 Hours
• Low Humidity, Last
24 Hours
• Average percent of
Capacity Last Hour
• Alarm History, Last
10 Alarms
• Equipment Runtimes
OPTIONAL FEATURES
• Analog Inputs
• RS-485 Network
• Two Additional
Remote Alarms
• Humidifier Flush
Rate
• Modulating
Humidifier Control
OPTIONS
Data Aire Remote Telecommunications
System - 200™
The Data Aire Remote
Telecommunications System - 200 (DART-200™ ) provides
comprehensive monitoring and control of Data Aire units via a phone modem to a
host PC station. The Data Aire units are interfaced with a communication module
(DART-Board) by a two wire connection. The DART-200 allows complete remote
control of Data Aire units through the unit mounted Data Alarm Processor-II and
retrieval of all historical data. Upon an alarm at the unit, the DART-Board
will automatically dial one or two pre-programmed numbers using an integral
modem and transmit specific alarm information. All entry or configuration capabilities
that are available at the Data Alarm Processor-II are accessible at the host station.
The commands or requests for data from each are processed through the
DART-Board. A single DART-Board will allow up to 32Data Aire units to be
connected and controlled. The DART-200 is capable of monitoring and controlling
up to 200 DART-Boards.
SYSTEM FEATURES
• Automatic Scrolling
of Current Status
• Automatic Scrolling
of Sensor Readings
• Sensor Database
• Sequential Display
of Alarms
• Password Access
• Multiple Audio
Alarm Modes
• Automatic Status
Log Prints
• Custom
"Help" Messages for Alarms
PROGRAMMABLE FUNCTIONS
• Temperature
Setpoint
• Humidity Sepoint
• Temperature High
Limit
• Humidity High Limit
• Temperature Low
Limit
• Humidity Low Limit
• Temperature
Sensitivity (Deadband)
• Humidity
Sensitivity (Deadband)
• On/Off/Standby
Operation
• Unit Rotation
• Unit ID Number
• Zone Number
• Password
MONITORED CONDITIONS
• Specific Alarms
from Unit(s)
• All Standard Alarms
from Unit(s)
• Programmed Local
Alarms from Unit(s)
• Current Operating
Mode
• Current Temperature
Sensor Readings
• Current Humidity
Sensor Readings
HISTORICAL DATA
• Alarm History for
Last 10 Alarms in Order of Occurrence and Time Since Detected
• Equipment Runtimes
for: Evaporator Motor, Compressor, Reheat, Humidification, Dehumidification
• Current and Average
Percent of Capacity for Last Hour
Remote Temperature & Humidity Sensors - Temperature and humidity
sensors may be ordered for remote wall mounting. Sensors are
provided in a wall mount plastic case for remote sensing of temperature and humidity.
25 feet of shielded cable is provided for field wiring.
Smoke Detector - A unit mounted smoke detector will shut down the unit if
smoke is sensed. The unit mounted microprocessor will sound an alarm and
display "SMOKE DETECTOR: UNIT SHUTDOWN" message. The smoke detector
is mounted in the return air stream and is provided with auxiliary contacts.
Unit Mounted Disconnect - A unit mounted non- automatic disconnect switch is
installed in the high voltage electrical section. The operating mechanism prevents
access to the high voltage electrical components until switched to the
"OFF" position. The operating mechanism (handle) protrudes through
the decorative door.Steam Generator Humidifier with Modulating Control - Modulating
control may be added to the steam generator humidifier. Modulating control will
allow the humidifier to automatically adjust steam output to match changing
room conditions. Self-regulating auto flush is included.
3-Way Water Regulating Valve - A 3- way water regulating valve for head pressure control
may be ordered to replace standard 2-way valve installed in unit. The 3-way
valve controls the water/glycol flow rate to meet the heat rejection
requirements under varying conditions.
Condensate Pump - Condensate pumps may ordered as
factory installed or for field installation. Condensate pumps are complete with
sump, motor, and automatic control. The pumps are rated for 130 GPH @ 20 foot
maximum or 40 GPH @ 20 feet with check valve. Pumps shipped loose are available
in 115, 230, or 460 volt. If unit mounted and wired, the pump will match the
unit voltage. Not available in 575 volt.
Upflow Plenum - Upflow plenums are fully insulated and have front discharge
air grille. Side grilles for both or one side are available. Plenums are 18
inches high and are painted to match the unit color.
Floorstand -
Floorstands are adjustable +/- 2 inches and may be ordered with a factory
installed turning vane or with seismic construction.
60 percent Efficient Filter - The standard 30 percent efficient filter may be replaced
with 60 percent efficient filter (based on ASHRAE Std. 52-76). Filters are 4
inch deep, pleated type. (Note: Higher efficiency filters are available - consult
factory regarding efficiency percentage and unit static pressures)
1" Pre-Filter - Units may be ordered with a one inch pre-filter.
Pump Package - Centrifugal pump packages are available to circulate water
or water/glycol solution. Pumps are available in various horsepower and voltage.
Both 3400 and 1750 rpm pumps are available as an option. Pumps ship loose or
come mounted in an optional pump enclosure.
Pump Auto-Changeover - Dual pump packages may be provided with a pump
auto-changeover control and NEMA 4 flow switch (field installed). The pump
auto-changeover control is factory wired and mounted in the dry cooler control
box. The pump auto-changeover control provides automatic pump changeover in the
event of a pump failure. Upon pump changeover, an audible alarm will sound at the
indoor unit and a message ("STANDBY PUMP ON: CHECK PRIMARY PUMP") will be displayed on the unit
microprocessor display.
Pump Enclosure - Pump enclosures are available for either single or dual
pump applications*. Pump enclosures are vented and weather resistant. When ordered
with pumps, the pumps are factory mounted in the enclosure ready for field
piping and wiring. (* Due to the size of some pumps, a special oversized
enclosure can be made available.)
Integral Pump Enclosures - Pumps may be factory mounted as an integral part of the dry
cooler. A 30" extension is added to the dry cooler. Pumps are pre-piped
and wired. Shut-off valves and flow switch are included. This configuration
greatly reduces field installation procedures.
Extended Compressor Warranties - Extended compressor warranties are available for periods of twenty-four (24) or forty-two (42) months in addition to the standard factory eighteen (18) month warranty. These warranties are for the replacement of compressors and do not include labor.